New: Transfomer Container Station - create a price information here

 

What functions does the Transfomer Container Station offer?

  • Conversion from medium voltage to low voltage
  • Switching of the medium voltage input (MVDB)
  • Distribution for the low voltage supply (LVMD)
  • Compensation of the phase shift
  • Determination of energy data

Which standards are used?

  • IEC 62271 / VDE 0671
  • TN-S, TN-C, TN-C-S System

The Transfomer Container Station is available in the following configurations:

  • Transfomer size 800 kVA, 1000 kVA, 1.200 kVA, 1.600 kVA are standard
  • On request, other sizes are available

What makes our Transformer Container Station so special?

  • Very fast commissioning because of ready-to-use container station
  • Nearly no interface clarification with building construction required
  • If there is no space inside of buildings, the installation of the container also can be done outdoors

 

System benefits

 

  • Construction of the container station according to European standards
  • Seefright sealing of the container for loading on ship
  • Maintenance-free, oil-cooled transformer
  • In case of extreme climates, air conditioning of the container is possible
  • Individual equipment of the switchgear and CB according to customer requirements possible
  • Global available services: inspection, overhaul, retrofit, remote support
  • Short spare part delivery
  • Training on the job
  • Short installation times
  • Plug and play solutions

 

Configuration data

 

Basic conditions:

  • Geographical installation height above mean sea level < 1000m
  • Minimum ambient temperature for machine installation area without air conditioning: +/- 0 °C
  • Maximum ambient temperature for machine installation area without air conditioning: +35 °C
  • Equipment is designed for indoor- or outdoor installation
  • Equipment is designed for the European supply market (others on request)

Electrical connection data:

  • Network configuration in the customer's network: TN-S, TN-C, TN-C-S network
  • Rated operating voltage in the customer's network: 360V~ up to 460V~
  • Rated frequency in the network: 50 or 60 Hz
  • Medium Voltage fluctuations in the customer`s network: max. +/- 10%
  • Medium Voltage Level up to 36 kV

Special specifications:

  • Extended TÜV certification is possible
  • Earthquake-proof variant is possible
  • Modifications to the design features required by the customer can result in changes to the scope of supply and can also cause adjustments to the delivery date and the price. Subject to technical changes
  • The electrical equipment is designed for the European delivery market

 

Transformer Container Station selection

 

Container_Station_800kVA

  • Efficient energy supply 250kVA - 700kVA
  • Container size 20" : 6,06m x 2,45m x 2,59m ; 5.800kg
  • Configure

Container_Station_1.000kVA

  • Efficient energy supply 350kVA - 900kVA
  • Container size 20" : 6,06m x 2,45m x 2,59m ; 6.300kg
Configure

Container_Station_1.250kVA

  • Efficient energy supply 500kVA - 1.100kVA
  • Container size 20" : 6,06m x 2,45m x 2,59m ; 6.800kg
Configure

Container_Station_1.600kVA

  • Efficient energy supply 600kVA - 1.450kVA
  • Container size 20" : 6,06m x 2,45m x 2,59m ; 7.400kg